Voltage : 12v Capacity : 5ah Weight : 1.9kg
Dimensions : 90mm Long X 70mm Wide X 106mm High (Over Terminals).
Terminals : 6.3mm / 0.250" Wide Male Spade Connection with square hole in terminal
Can be used to replace: Y5-12, NP5-12, NPG5-12, NP5-12, NPH5-12, NP4.5-12
Design life : 3 - 5 Year design life when used in standby applications.
Commonly used in UPS Systems ,Alarm Systems, Emergency Lighting, Ride on Toys, Torches and other electrical systems and Belkin models FC6110
Price: £15.29
Price With Tax: £18.35
SPECIFICATIONS |
||
Nominal voltage |
12 |
V |
20-hr rate Capacity to 1.75VPC at 20°C |
5 |
Ah |
10-hr rate Capacity to 1.75VPC at 20°C |
4.63 |
Ah |
DIMENSIONS |
||
Length |
90 (±1) |
mm |
Width |
70 (±1) |
mm |
Height |
101 (±1) |
mm |
(height over terminals) |
107 (±2) |
mm |
Mass (typical) |
1.68 |
kg |
TERMINAL TYPE |
||
FASTON (Quickfit / release) |
6.35 |
mm |
OPERATING TEMPERATURE RANGE |
||
Storage |
-20°C to +60°C |
|
Charge |
-15°C to +50°C |
|
Discharge |
-20°C to +60°C |
|
STORAGE |
||
Capacity loss per month at 20°C (approx) |
3 |
% |
CASE MATERIAL |
||
Standard Option |
ABS (UL.94:HB) |
|
Flame retardant option (FR) |
ABS (UL94:V0) |
|
CHARGE VOLTAGE |
||
Float charge voltage at 20°C |
13.65 (±1%) |
V |
2.275 (±1%) |
V/cell |
|
Float Charge voltage temperature correction factor (for variations from the standard 20°C) |
-3 |
mV/cell/°C |
Cyclic (or Boost) charge at 20°C |
14.5 (±3%) |
V |
2.42 (±3%) |
V/cell |
|
Cyclic Charge voltage temperature correction factor (for variations from the standard 20°C) |
-4 |
mV/cell/°C |
CHARGE CURRENT |
||
Float charge current limit |
No limit |
A |
Cyclic (or Boost) charge current limit |
1.25 |
A |
MAXIMUM DISCHARGE CURRENT |
||
1 minute |
50 |
A |
SHORT-CIRCUIT CURRENT & INTERNAL RESISTANCE |
||
(according to EN IEC 60896-21) |
||
Internal resistance |
N/A |
m! |
Short-Circuit current |
N/A |
A |
IMPEDANCE |
||
Measured at 1 kHz |
45 |
m! |
PERFORMANCE & CHARACTERISTICS |
||
Refer to the technical manual |
YUCEL |
|
DESIGN LIFE |
||
EUROBAT Classification: Standard Commercial |
3 to 5 |
years |
Yuasa design life @ 20°C |
up to 5 |
years |
SAFETY |
||
Installation Can be installed and operated in any orientation except permanently inverted |
||
Handles Batteries must not be suspended by their handles (where fitted) |
||
Vent valves Each cell is fitted with a low pressure release valve to allow gasses to escape and then reseal. |
||
Gas Release VRLA Batteries release hydrogen gas which can form explosive mixtures in air. Do not place inside a sealed container |
||
Recycling YUASA's VRLA batteries must be recycled at the end of life in accordance with local and national laws and regulations |